Ball Float Steam Traps belong to the family of mechanical traps. They operate on the difference in density between steam and water.
Ball Float Steam Traps belong to the family of mechanical traps. They operate on the difference in density between steam and water.
Ball Float Steam Traps belong to the family of mechanical traps. They operate on the difference in density between steam and water.
G11N & G12N | Cast Iron Steam Traps for small and medium condensate loads | |||
G15N | Cast Iron Steam Trap for low pressure and large condensate loads | |||
G3N – G5, G2 – G8 | Cast Iron Steam Traps for large condensate loads | |||
G20 | Cast Iron Steam Trap for medium condensate loads | |||
GH3N – GH5, GH2 – GH8, GH50, GH60 | Cast Steel Steam Traps for large condensate loads | |||
GH40, GTH12 | Cast Steel Steam Traps for medium condensate loads | |||
GC1, GC1V | Stainless Steel Steam Traps for small condensate loads | |||
GC20 | Stainless Steel Steam Trap for medium condensate loads |
|
Ball Float Steam Traps can be used in all process applications, like all kind of heat exchangers, tank and unit heaters and others, where condensate must be removed immediately after it forms. The type GC1 is especially designed for applications in the food, pharmaceutical and other industries with small condensate loads and the need for stainless steel bodies. It can be also installed for drainage of steam main lines. |
cold condensate hot condensate steam/hot air |
On start-up air is quickly discharged through the thermostatic air vent (membrane or bimetal type). Cold condensate fills the steam trap body.
As soon as a certain water level is reached, the float rises and opens the valve. The cold condensate is discharged through the open valve and the open air vent.
The opening degree of the valve is regulated by the water level inside the trap body. Condensate is discharged continuously.
As long as air enters the trap and accumulates at the top of the trap body, the temperature cools down a little bit and the air vent, which opens slightly below saturation temperature, begins to discharge the air from the trap.